SIEMENS
2/665
Siemens IK PI · 2015
PROFINET/Industrial Ethernet
Accessories
C-PLUG
2
■
Function
During start-up, the device automatically backs up the configu-
ration data on an unwritten C-PLUG (delivery condition) that has
been plugged into a SIMATIC NET component. Changes to the
configuration during normal operation are also backed up on the
C-PLUG without any additional operator intervention.
During start-up an unconfigured device automatically loads the
configuration data from an inserted, written C-PLUG provided
the data were written by a compatible device type.
Diagnostics
Incorrect C-PLUG handling, such as inserting a C-PLUG that
contains the configuration of another device group or general
malfunctions of the C-PLUG are signaled over the diagnostic
mechanisms for the respective data terminal (LEDs, PROFINET,
SNMP, Web-based Management, etc.).
■
Integration
Supported products
SCALANCE X Industrial Ethernet switches
•
SCALANCE X-200
•
SCALANCE X-300 (included in scope of supply)
•
SCALANCE X-400 (included in scope of supply)
•
SCALANCE X-500 (included in scope of supply)
SCALANCE S security modules
•
SCALANCE S -600
Industrial Wireless LAN SCALANCE W
•
W78x, W77x IWLAN Access Points
•
W74x, W76x IWLAN Client Modules
SCALANCE M industrial modems and routers
•
SCALANCE M81x
•
SCALANCE M826
•
SCALANCE M874
System connections for SIMATIC S7
•
CP 443-1 Advanced (included in delivery)
•
CP 343-1 Advanced (included in delivery)
•
CP 343-1 ERPC (included in delivery)
Network transitions
•
IE/PB Link PN IO
•
IE/AS-i LINK PN IO
•
DP/AS-i LINK Advanced
■
Technical specifications
■
Ordering data
Article No.
Product-type designation
C-PLUG
Supply voltage
Via terminal device
Power loss
0.015 mW
Installation
Can be plugged into C-PLUG slot
Constructional design
• Dimensions (W x H x D) in mm
24.3 x 17 x 8.1
• Weight
Approx. 5 g
Memory capacity
32 MB
Degree of protection
IP20
C-PLUG
6GK1900-0AB00
Swap medium for simple
replacement of devices in the
event of a fault;
for storing configuration or
engineering and application data;
can be used for SIMATIC NET
products with PLUG slot
© Siemens AG 2014