SIEMENS
2/731
Siemens IK PI · 2015
2
■
Technical specifications
(continued)
PROFINET/Industrial Ethernet
SIMATIC ET 200pro
Interface modules
IM 154-8 PN/DP CPU
1st interface
Interface type
Integrated RS 485 interface
Physics
RS 485/connection:
2 x M12 b-coded
Functionality
• MPI
Yes
• DP master
Yes
• DP slave
Yes
• Point-to-point connection
No
DP master
• Number of DP slaves, max.
124
2nd interface
Interface type
PROFINET
Physics
Ethernet
(2 x M12 d-coded; 1 x RJ45)
Number of ports
3
Functionality
• MPI
No
• DP master
No
• DP slave
No
• PROFINET IO Controller
Yes; Also simultaneously
with IO-Device functionality
• PROFINET IO Device
Yes; Also simultaneously
with IO Controller functionality
• PROFINET CBA
Yes
PROFINET IO Controller
• Max. number of connectable IO
devices for RT
128
• Number of IO devices with IRT
and the option "high flexibility"
128
• Number of IO Devices with IRT
and the option "high performance",
max.
64
Isochronous mode
Isochronous operation
(application synchronized
up to terminal)
Yes;
Via PROFIBUS DP or
PROFINET interface
6ES7154-8AB01-0AB0
IM 154-8 PN/DP CPU
Communication functions
PG/OP communication
Yes
Global data communication
• supported
Yes
S7 basic communication
• supported
Yes
S7 communication
• supported
Yes
Open IE communication
• TCP/IP
Yes;
via integrated PROFINET interface
and loadable FBs
-
Number of connections, max.
8
• ISO-on-TCP (RFC1006)
Yes
-
Number of connections, max.
8
• UDP
Yes
-
Number of connections, max.
8
Web server
• supported
Yes
Configuration
programming
• Programming language
- LAD
Yes
- FBD
Yes
- STL
Yes
- SCL
Yes
- CFC
Yes
- GRAPH
Yes
- HiGraph®
Yes
Know-how protection
• User program protection/password
protection
Yes
• Block encryption
Yes; With S7 block Privacy
Dimensions
Width
135 mm
Height
130 mm
Depth
65 mm;
60 mm without cover for RJ45 socket;
65 mm with cover for RJ45 socket
Weights
Weight, approx.
720 g
6ES7154-8AB01-0AB0