SIEMENS
2/724
Siemens IK PI · 2015
PROFINET/Industrial Ethernet
SIMATIC ET 200M
Interface modules
IM 153-4 PN
2
■
Overview
•
To connect ET 200M to PROFINET IO (via copper line, RJ45)
as an IO device
•
2 versions:
- IM 153-4 PN STANDARD
- IM 153-4 PN HIGH FEATURE:
supports, in contrast to the STANDARD version, the
operation of PROFIsafe F and HART modules. The operation
of an S7-400H (system redundancy) is likewise possible.
•
Integrated 2-port switch
•
12 modules per station
•
Usable I/O capacity: 192 bytes each
•
Active bus backplane to hot-swap modules available as an
option
•
Baud rate 10 Mbit/s / 100 Mbit/s (autonegotiation / full duplex)
•
I&M functions according to PNO-Guideline Order-No. 3.502,
Version V1.1
Note:
Micro Memory Card with at least 64 KB required if not all the
stations in the network support LLDP (Link Layer Discovery
Protocol; proximity detection).
■
Technical specifications
6ES7153-4AA01-0XB0
6ES7153-4BA00-0XB0
IM 153-4 PN STANDARD
IM 153-4 PN HIGH FEATURE
General information
Vendor identification (VendorID)
002AH
002AH
Device identifier (DeviceID)
0302H
0302H
Supply voltage
24 V DC
Yes
Yes
permissible range, lower limit (DC)
20.4 V
20.4 V
permissible range, upper limit (DC)
28.8 V
28.8 V
permissible range (ripple included),
lower limit (DC)
20.4 V
18.5 V
permissible range (ripple included),
upper limit (DC)
28.8 V
30.2 V
External protection for supply cables
(recommendation)
In a construction with grounded reference potential,
a fuse is necessary for redundant interface modules
(Recommendation: 2.5 A)
In a construction with grounded reference potential,
a fuse is necessary for redundant interface modules
(Recommendation: 2.5 A)
Mains buffering
• Mains/voltage failure stored energy
time
5 ms
5 ms
Input current
Current consumption, max.
600 mA
600 mA
Inrush current, typ.
4 A
4 A
I²t
0.09 A²·s
0.09 A²·s
© Siemens AG 2014