SIEMENS
2/721
Siemens IK PI · 2015
PROFINET/Industrial Ethernet
SIMATIC ET 200MP
Interface modules
IM 155-5 PN
2
■
Overview
•
Interface modules for linking the ET 200MP to PROFINET
•
These handle data exchange with the PROFINET I/O controller
in the PLC
•
Integrated 2-port switch for line topology
•
Max. 30 I/O modules
•
Shortest bus cycle 250 μs
•
Linking to the isochronous task of the CPU
•
Prioritized fast startup (FSU) with 500 ms
(max. 12 I/O modules)
•
Media Redundancy Protocol (MRP)
•
Shared device on up to two I/O controllers (when configuring
using GSD file; depends on the respective configuration tool)
•
Omission of SIMATIC memory card (SMC); IM replacement
without PG using LLDP
Starting from FW version V2.0.0, the IM155-5 PN ST interface
module supports the following new functions:
•
Submodule-granular shared device with up to two I/O
controllers
•
Configuration control (option handling)
•
Module-internal shared input and output (MSI/MSO), i.e. the
inputs or outputs of a module can be made available simulta-
neously to up to two I/O controllers
The IM155-5 PN HF interface module has the following
additional functions:
•
Shared device on up to 4 IO controllers
•
Module-internal shared input and output (MSI/MSO) on up to
four IO controllers
•
Operation on a highly available SIMATIC S7-400H
•
Support for the MRPD function (media redundancy with
planned duplication)
■
Technical specifications
6ES7155-5AA00-0AB0
6ES7155-5AA00-0AC0
IM 155-5 PN ST
IM 155-5 PN HF
General information
Product function
• I&M data
Yes; I&M0 to I&M3
Yes; I&M0 to I&M3
Engineering with
• STEP 7 TIA Portal can be
configured/integrated as of version
V13 / V13
V13 / V13
• STEP 7 can be
configured/integrated as of version
V5.5 SP3 / -
V5.5 SP3 / -
• PROFINET
as of GSD version/GSD revision
V2.3 / -
V2.3 / -
Supply voltage
Type of supply voltage
DC
DC
Rated value (DC)
24 V
24 V
Reverse polarity protection
Yes
Yes
Short-circuit protection
Yes
Yes
Mains buffering
• Mains/voltage failure stored energy
time
5 ms
5 ms
Hardware configuration
Integrated power supply
Yes
Rack
• Modules per rack, max.
30; I/O modules
30; I/O modules
Interfaces
Number of PROFINET interfaces
1
1
1st interface
• Interface types
-
Number of ports
2
2
-
Integrated switch
Yes
Yes
-
RJ 45 (Ethernet)
Yes
Yes
• Protocols
-
PROFINET IO Device
Yes
Yes
-
Media redundancy
Yes
Yes
© Siemens AG 2014