SIEMENS
2/696
Siemens IK PI · 2015
■
Design
(continued)
PROFINET/Industrial Ethernet
SIMATIC PCS 7 process control systems
Complementary S7-400 systems
2
Runtime licenses
Each automation system is already provided as standard
with the SIMATIC PCS 7 Industry Library Runtime and the
SIMATIC PCS 7 AS Runtime license for 100 process objects (PO);
safety-oriented automation systems additionally with the S7
F Systems RT license. The 100 POs of the SIMATIC PCS 7
AS Runtime license can be expanded by additional Runtime
licenses for 100, 1 000 or 10 000 POs. The process objects of
additional Runtime licenses can be added to process objects
which already exist. The number and type (e.g. 100 or 1 000) of
additional Runtime licenses are irrelevant.
Individual configuration of AS bundles
The various versions of the SIMATIC PCS 7 automation systems
AS 412 to AS 417 are available as AS bundles as follows:
•
Individual components, combined per station in one
consignment
•
Preassembled and tested complete systems (no extra charge
compared to delivery of individual components)
Typical combinations can be selected from tables in the section
"Ordering data".
The complete range is available to you via two configurators in
the Industry Mall (
www.siemens.com/industrymall
):
•
SIMATIC PCS 7 AS Single Station configurator
•
SIMATIC PCS 7 AS Redundancy Station configurator
Ordering notes
•
For a redundant configuration based on 2 AS Single Stations,
you additionally require 4 sync modules (up to 10 m or 10 km)
and 2 fiber-optic sync cables. The selection depends on the
distance between the two AS Single Stations.
•
FO sync cables longer than 1 m must always be ordered
separately (2 cables required in each case).
■
Ordering data
Article No.
Configuration tables
for standard automation systems
1)
With the UR2 rack in combination with a redundant power supply,
the number of additive CP 443-5 Extended is limited to 3.
AS 414-3IE
with SIMATIC PCS 7 AS Runtime
license for 100 POs
CPU with 2 DP interfaces
(MPI/DP and slot for IF module)
4 MByte main memory
(2 MByte each for program and data)
6ES7654-
7
7
7
7
7
-
7
7
F
7
Type of delivery
• Individual components,
not pre-assembled
7
• Pre-assembled and tested
8
Memory card
• Memory card 2 MB RAM
(up to approx. 100 POs)
B
• Memory card 4 MB RAM
(up to approx. 210 POs)
C
• Memory card 8 MB RAM
(up to approx. 800 POs)
D
CPU type
• CPU 414-3 PN/DP
(up to approx. 350 POs)
D
Additive IF 964-DP interface module
• Without additive IF 964-DP
0
• 1 x IF 964-DP
1
Interface to Industrial Ethernet/
PROFINET plant bus
• integrated, without CP 443-1
0
• 1 × CP 443-1EX30
3
• 2 × CP 443-1EX30
4
Racks
• UR2 (9 slots), aluminum
3
• UR2 (9 slots), steel
4
• UR1 (18 slots), aluminum
5
• UR1 (18 slots), steel
6
Power supply
(without backup batteries)
• 1 x PS 407,
10 A for 120/230 V AC/DC
B
• 1 x PS 407,
10 A for 120/230 V AC/DC,
optional redundancy
C
• 1 x PS 407,
20 A for 120/230 V AC/DC
D
• 2 x PS 407,
10 A for 120/230 V AC/DC,
optional redundancy
E
• 1 x PS 405, 10 A for 24 V DC
G
• 1 x PS 405, 10 A for 24 V DC,
optional redundancy
H
• 1 x PS 405, 20 A for 24 V DC
J
• 2 x PS 405, 10 A for 24 V DC,
optional redundancy
K
Additive PROFIBUS DP interfaces
• Without CP 443-5 Extended
0
• 1 x CP 443-5 Extended
1
• 2 x CP 443-5 Extended
2
• 3 x CP 443-5 Extended
3
• 4 x CP 443-5 Extended
1)
4
© Siemens AG 2014