SIEMENS
2/687
Siemens IK PI · 2015
■
Design
(continued)
PROFINET/Industrial Ethernet
SIMATIC PCS 7 process control systems
Fault-tolerant automation systems
2
Communication via the Industrial Ethernet (IE) plant bus
If the PROFINET interface integrated in the CPUs of the AS 410H
is not used for PROFINET IO, it can also be used for the connec-
tion to the Industrial Ethernet plant bus. Otherwise, the two sub-
systems of the AS
410H can be connected to the plant bus using
one CP 443-1 communication module (conformal coating) each.
The plant bus can be implemented in the form of a ring structure,
which can also be configured with redundant architecture if the
availability requirements are high. When there are two redundant
rings it makes sense to use two communications processors in
each case and to distribute their connections between the two
rings (4-way connection). Double faults such as failure of the
switch on ring 1 with simultaneous interruption of the bus cable
on ring 2 can thus be tolerated.
Runtime licenses
With SIMATIC PCS 7 Industry Library Runtime and the
SIMATIC
PCS
7 AS
Runtime license, the automation systems are
equipped with 100 process objects (PO) on delivery. The num-
ber of process objects can be extended by additional Runtime
licenses for 100, 1 000 or 10 000 POs. The process objects of
additional Runtime licenses can be added to process objects
which already exist. The number and type (e.g. 100 or 1 000) of
additional Runtime licenses are irrelevant.
■
Ordering data
Article No.
1)
In configurations with UR2/UR2-H racks, up to 5 CPs (Industrial Ethernet/
PROFIBUS) can be configured with a single power supply, or up to 3 CPs
for each subsystem with a redundant power supply.
AS 410H (Redundancy Station)
2 x CPU 410-5H with PROFIBUS DP
and PROFINET IO interface
32 MB RAM (16 MB each for pro-
gram and data) with SIMATIC PCS 7
AS Runtime license for 100 PO and
SIMATIC PCS 7 Industry Library
Runtime license
6ES7656-
7
C
7
7
7
-
7
7
F
7
Type of delivery
• Individual components,
not pre-assembled
5
• Pre-assembled and tested
6
System expansion card
• 2 x System expansion card
100 POs
J
• 2 x System expansion card
500 POs
L
• 2 x System expansion card
1 000 POs
N
• 2 x System expansion card
1 600 POs
P
•
2 x System expansion card PO
2k+
(
2 000)
Q
Sync modules and cables
• 2 x 2 sync modules for distances
up to 10 m and 2 x FO sync cable,
1 m
3
• 2 x 2 sync modules for up to 10 km
and 2 x FO sync cable, 1 m, for
testing
4
Additive Industrial Ethernet
interfaces
1)
• Without CP 443-1
0
• 2 x 1 CP 443-1 (conformal coating)
3
• 2 x 2 CP 443-1 (conformal coating)
4
Racks
• 1 x UR2-H (2 x 9 slots), aluminum
1)
1
• 1 x UR2-H (2 x 9 slots), steel
1)
2
• 2 x UR2 (9 slots), aluminum
1)
3
• 2 x UR2 (9 slots), steel
1)
4
Power supply
(without backup batteries)
• 2 x PS 407, 10 A
for 120/230 V AC/DC
B
• 2 x PS 407, 10 A
for 120/230 V AC/DC,
optional redundancy
C
• 2 x PS 407, 20 A
for 120/230 V AC/DC
D
• 2 x 2 PS 407, 10 A
for 120/230 V AC/DC, redundant
E
• 2 x PS 405, 10 A for 24 V DC
G
• 2 x PS 405, 10 A for 24 V DC,
optional redundancy
H
• 2 x PS 405, 20 A for 24 V DC
J
• 2 x 2 PS 405, 10 A for 24 V DC,
redundant
K
Additive PROFIBUS DP
interfaces
1)
• Without CP 443-5 Extended
0
• 2 x 1 CP 443-5 Extended
(conformal coating)
1
• 2 x 2 CP 443-5 Extended
(conformal coating)
2
• 2 x 3 CP 443-5 Extended
(conformal coating)
3
• 2 x 4 CP 443-5 Extended
(conformal coating)
4
© Siemens AG 2014