SIEMENS
2/547
Siemens IK PI · 2015
2
■
Technical specifications
(continued)
PROFINET/Industrial Ethernet
Communication for SIMATIC S7-300
CP 343-1 Lean
Performance data
Performance data
open communication
Number of possible connections
for open communication by means
of SEND/RECEIVE blocks maximum
8
Data volume
• as user data per ISO on TCP con-
nection for open communication by
means of SEND/RECEIVE blocks
maximum
8 Kibyte
• as user data per TCP connection
for open communication by
means of SEND/RECEIVE blocks
maximum
8 Kibyte
• as user data per UDP connection
for open IE communication by
means of SEND/RECEIVE blocks
maximum
2 Kibyte
Number of Multicast stations
8
Performance data
S7 communication
Number of possible connections for
S7 communication
• maximum
4
Service of SIMATIC communication as
server
Yes
Performance data
multi-protocol mode
Number of active connections with
multiprotocol mode
12
Performance data
PROFINET communication
as PN IO-Device
Product function PROFINET IO
device
Yes
Amount of data
• as useful data for input variables
as PROFINET IO device maximum
512 byte
• as useful data for input variables
as PROFINET IO device maximum
512 byte
• as useful data for input variables
for each sub-module under
PROFINET IO device
240 byte
• as useful data for input variables
for each sub-module under
PROFINET IO device
240 byte
• as useful data for the consistency
area for each sub-module
240 byte
Number of submodules
per PROFINET IO-Device
32
Article No.
6GK7343-1CX10-0XE0
Product-type designation
CP 343-1 Lean
Product functions
management,
configuration
Product function MIB support
Yes
Protocol is supported
• SNMP v1
Yes
• DCP
Yes
• LLDP
Yes
Configuration software required
STEP 7 V5.4 or higher /
STEP 7 Professional V11 (TIA Portal)
or higher
Identification & maintenance function
• I&M0 - device-specific information
Yes
• I&M1 - higher level
designation/location designation
Yes
Product functions
Diagnosis
Product function Web-based
diagnostics
Yes
Product functions
switch
Product feature switch
Yes
Product function
• switch-managed
No
• Configuration with STEP 7
Yes
Product functions
Redundancy
Product function
• Ring redundancy
Yes
• Media Redundancy Protocol
(MRP)
Yes
Product functions
Security
Product function
• switchoff of non-required services
Yes
• blocking of communication
via physical ports
Yes
Product functions
Time
Product function
• SICLOCK support
Yes
• pass on time synchronization
Yes
Protocol is supported NTP
Yes
Article No.
6GK7343-1CX10-0XE0
Product-type designation
CP 343-1 Lean
© Siemens AG 2014