SIEMENS
2/542
Siemens IK PI · 2015
PROFINET/Industrial Ethernet
Communication for SIMATIC S7-200
CP 243-1
2
■
Function
The CP 243-1 is connected to Industrial Ethernet via an
RJ45 interface for 10/100 Mbit/s full/half duplex with
autosensing/autonegotiation and autocrossover function.
The CP 243-1 enables communication between an
S7-200 module and another S7-200 or S7-300/S7-400 controller
via Industrial Ethernet, and access of the S7-200 programming
software STEP 7-Micro/WIN to the S7-200 via Industrial Ethernet.
Integration into PC applications is possible by means of the
S7-OPC server of the PC software.
IT functions
Simple visualization using Web technology, sending e-mails,
and file processing (FTP).
The file system of the CP 243-1 can also be managed through
the CPU. It is used as a bulk storage device, a cross-system
computer link and a storage location for HTML pages and Java
applets. The CP 243-1 has a large file system in which, apart
from HTML pages, machine documentation or user guides can
also be stored.
Web server;
HTML pages can be downloaded and viewed with standard
browsers
Web pages
•
For observation of the S7-200 controller:
standard pages for system diagnostics and a simple variable
editor are supplied.
•
Other customer-specific pages can be generated with any
HTML tools
E-mails;
sending of pre-defined e-mails directly from the user program
Variables can be integrated into the text
FTP communication
The CPU can send data blocks as files to other computers or can
read or delete the files of other computers (client function). Com-
munication through FTP is possible with most operating systems
Configuration
•
STEP 7 Micro/WIN V4.0 SP8 or higher is required for config-
uring the full functional scope of the CP 243-1.
•
The CP 243-1 is supplied with a globally unique MAC address
that cannot be changed.
■
Integration
S7-200 communication options with CP 243-1
Cell phone/PDA
Notebook
S7-400
with CP 443-1
S7-300
with CP 343-1
Advanced
Linux, DOS,
UNIX, Mainframe
via FTP
PC with application
(e.g. WinCC, WinAC)
via OPC or
Internet browser
Embedded System
(e.g. nutrunner,
welding control )
via FTP
Alarm via
email/sms
Alarm via
email/sms
Industrial Ethernet
PROFIBUS
SCALANCE
S613
Internet
Router
AS-Interface
S7-200
S7-200
IO
EM 277
CP 243-2
CP 243-1
CP 243-1
Field PG
IO
G_IK10_XX_10287
© Siemens AG 2014