SIEMENS
2/537
Siemens IK PI · 2015
PROFINET/Industrial Ethernet
Communication for SIMATIC S7-1500
CP 1543-1
2
■
Design
The CP 1543-1 features all the advantages of the
SIMATIC S7-1500 design:
•
Compact design:
- One RJ45 jack for connecting to Industrial Ethernet;
automatic data rate detection using autosensing,
autocrossing and autonegotiation;
the connection is made via the IE FC RJ45 Plug 180 with
180° cable outlet or via a standard patch cable
- The module is supplied with power via the integrated
backplane bus
- Three LEDs for displaying the operational and communica-
tions status of the module and one LED under the front cover
for the Ethernet interface to display ACTIVITY and LINK.
•
Simple installation:
The CP 1543-1 is mounted on the rail of the S7-1500 and
connected to the adjacent modules by means of the bus
connectors.
•
The CP 1543-1 can be operated without a fan; no backup
battery is required.
•
The module can be replaced without the need for a
programming device.
■
Function
•
Gigabit interface with an RJ45 connector with
10/100/1 000 Mbps full/half duplex with autosensing
functionality
•
Communication services:
- Open communication (TCP/IP, UDP, ISO):
Multicast with UDP
- PG/OP communication: inter-network with S7 routing
- S7 communication (client, server)
- IT communication:
HTTP communication allows access to the Web server of the
S7-1500 system. With the CP
1543-1, HTTPS communication
is also possible.
The e-mail client function allows the sending of e-mails
directly from the user program.
FTP communication allows program-controlled FTP client
communication.
Access to data blocks in the CPU via FTP server.
-
IP address assignment using DHCP with IPv4 or by entering
the address directly in the engineering software
STEP 7 Professional V12 or higher (TIA Portal)
•
Diagnostics and network management:
- Extensive diagnostics functions for all modules in the
S7-1500 system
- Integration in network management systems due to support
of SNMP V1/V3
•
Security mechanisms:
- Access protection with firewall for filtering connections on
the basis of their IP and MAC addresses
- Secure communication via VPN (IPsec)
- Encrypted HTML pages using SSL (HTTPS)
- Secure file transfer (FTPS)
- Tap-proof transfer of network analysis information to the
network management system (SNMPv3)
- Secure transfer of the time of day (NTP)
•
Configuration of all functions with STEP 7 Professional V13
(TIA Portal) or higher
•
Module replacement without programming device:
All information can be stored on the memory card of the CPU.
© Siemens AG 2014