Technical specifications
(continued)
PROFINET/Industrial Ethernet
Controllers / PC-based controllers
SIMATIC WinAC RTX F
Functionality
• PROFINET IO Controller
Yes
• PROFINET IO Device
No
• PROFINET CBA
Yes
• Open IE communication
Yes
PROFINET IO Controller
• Transmission rate, min.
100 Mbit/s
• Transmission rate, max.
100 Mbit/s
• Number of connectable IO devices,
max.
128
• Max. number of connectable
IO devices for RT
128
-
of which in line, max.
128
• IRT, supported
No
• Prioritized startup supported
Yes
-
Number of IO Devices, max.
32
• Activation/deactivation of
IO Devices
Yes
-
Maximum number of IO devices
that can be activated/deactivated
at the same time.
8
• IO Devices changing during opera-
tion (partner ports), supported
Yes
• Device replacement without swap
medium
Yes
• Send cycles
1 ms
• Updating time
1 - 512 ms (minimum value depends
on communication share set for
PROFINET I/O, on the number
of I/O devices, and on the volume of
configured user data)
• Services
-
PG/OP communication
Yes
- Routing
Yes; S7 routing
-
S7 communication
Yes
-
Isochronous mode
No
-
Open IE communication
Yes
• Address area
-
Inputs, max.
16 kbyte
-
Outputs, max.
16 kbyte
-
User data per address area, max.
2 kbyte
-
User data consistency, max.
254 byte
PROFINET CBA
• acyclic transmission
Yes
• Cyclic transmission
Yes
SIMATIC communication
• PG/OP communication
Yes
• S7 routing
Yes
• S7 communication
Yes
• Number of connections, max.
16
Open IE communication
• Open IE communication, supported
Yes
• Number of connections, max.
32
• Local port numbers used at the
system end
0, 20, 21, 23, 25, 80, 102, 135, 161,
8080, 34962, 34963, 34964, 65532,
65533, 65534, 65535
• Keep-alive function, supported
Yes
6ES7671-1RC08-0YA0
SIMATIC WinAC RTX F 2010
4th interface
Interface type
PROFINET
Max. no. of simultaneously operable
CPs
1
Physics
Ethernet
Isolated
Yes
Integrated switch
Yes
Number of ports
3
Automatic detection of transmission
speed
Yes; 10/100 Mbit/s
Autonegotiation
Yes
Autocrossing
Yes
Change of IP address at runtime,
supported
Yes
Number of connection resources
32
Media redundancy
• supported
Yes
• Switchover time on line break,
typically
200 ms
• Number of stations in the ring, max.
50
Functionality
• PROFINET IO Controller
Yes
• PROFINET IO Device
No
• PROFINET CBA
Yes
• Open IE communication
Yes
• Web server
Yes
PROFINET IO Controller
• Transmission rate, max.
100 Mbit/s
• Max. number of connectable
IO devices for RT
256
-
of which in line, max.
256
• Number of IO devices with IRT and
the option "high flexibility"
64
-
of which in line, max.
32
• Number of IO Devices with IRT and
the option "high performance", max.
64
-
of which in line, max.
64
• IRT, supported
Yes
• Prioritized startup supported
Yes
-
Number of IO Devices, max.
32
• Activation/deactivation of
IO Devices
Yes
-
Maximum number of IO devices
that can be activated/deactivated
at the same time.
8
• IO Devices changing during opera-
tion (partner ports), supported
Yes
• Device replacement without swap
medium
Yes
• Send cycles
250 μs, 500 μs, 1 ms
• Updating time
0.25...512
depending on the send cycle
• Services
-
PG/OP communication
Yes
- Routing
Yes; S7 routing
-
S7 communication
Yes
-
Isochronous mode
Yes
-
Open IE communication
Yes
6ES7671-1RC08-0YA0