SIEMENS
2/501
Siemens IK PI · 2015
2
■
Technical specifications
(continued)
PROFINET/Industrial Ethernet
Controllers / PC-based controllers
SIMATIC WinAC RTX
Media redundancy
• supported
Yes
• Switchover time on line break,
typically
200 ms
• Number of stations in the ring, max.
50
Functionality
• PROFINET IO Controller
Yes
• PROFINET IO Device
No
• PROFINET CBA
Yes
• Open IE communication
Yes
• Web server
Yes
PROFINET IO Controller
• Transmission rate, max.
100 Mbit/s
• Max. number of connectable
IO devices for RT
256
-
of which in line, max.
256
• Number of IO devices with IRT and
the option "high flexibility"
64
-
of which in line, max.
32
• Number of IO Devices with IRT and
the option "high performance", max.
64
-
of which in line, max.
32
• IRT, supported
Yes
• Prioritized startup supported
Yes
-
Number of IO Devices, max.
32
• Activation/deactivation of
IO Devices
Yes
-
Maximum number of IO devices
that can be activated/deactivated
at the same time.
8
• IO Devices changing during opera-
tion (partner ports), supported
Yes
• Device replacement
without swap medium
Yes
• Send cycles
250 μs, 500 μs, 1 ms
• Updating time
0.25...512 depending on the send
cycle
• Services
-
PG/OP communication
Yes
- Routing
Yes; S7 routing
-
S7 communication
Yes
-
Isochronous mode
Yes
-
Open IE communication
Yes
• Address area
-
Inputs, max.
16 kbyte
-
Outputs, max.
16 kbyte
-
User data per address area, max.
2 kbyte
-
User data consistency, max.
254 byte
SIMATIC communication
• PG/OP communication
Yes
• S7 routing
Yes
• S7 communication
Yes
• Number of connections, max.
32
Open IE communication
• Open IE communication, supported
Yes
• Number of connections, max.
32
• Local port numbers used
at the system end
0, 20, 21, 25, 80, 102, 135, 161,
34962, 34963, 34964, 65532, 65533,
65534, 65535
Isochronous mode
Isochronous operation (application
synchronized up to terminal)
Yes
Number of DP masters with
isochronous mode
2
User data per isochronous slave,
max.
128 byte
equidistance
Yes
shortest clock pulse
2.2 ms;
2.2 ms without partial process image;
2.2 ms with partial process image
6ES7671-0RC08-0YA0
SIMATIC WinAC RTX 2010
Communication functions
PG/OP communication
Yes
Data record routing
Yes; Only with CP 5611 or integrated
PROFIBUS interface of the
SIMATIC PC
Global data communication
• supported
No
S7 basic communication
• supported
No
S7 communication
• supported
Yes
• as server
Yes
• As client
Yes
• User data per job, max.
64 kbyte;
When using BSEND/USEND
Open IE communication
• TCP/IP
Yes
-
Number of connections, max.
32
-
Data length for connection type
01H, max.
Not supported
-
Data length for connection type
11H, max.
65 534 byte
-
Data length, max.
65 534 byte
• ISO-on-TCP (RFC1006)
Yes
-
Number of connections, max.
32
-
Data length, max.
65 534 byte
• UDP
Yes
-
Number of connections, max.
32
-
Data length, max.
1 472 byte
Web server
• supported
Yes
• Number of HTTP clients
2
• User-defined websites
No
PROFINET CBA
(at set setpoint communication load)
• Setpoint for the CPU
communication load
20 %
• Number of remote
interconnection partners
64
• Number of functions, master/slave
30
• Total of all Master/Slave
connections
1 000
• Data length of all incoming
connections master/slave, max.
6 800 byte
• Data length of all outgoing
connections master/slave, max.
6 800 byte
• Number of device-internal and
PROFIBUS interconnections
500
• Data length of device-internal and
PROFIBUS interconnections, max.
4 000 byte
• Data length per connection, max.
1 400 byte
• Remote interconnections
with acyclic transmission
-
Sampling frequency:
Sampling time, min.
500 ms
-
Number of incoming
interconnections
100
-
Number of outgoing
interconnections
100
-
Data length of all incoming
interconnections, max.
2 000 byte
-
Data length of all outgoing
interconnections, max.
2 000 byte
-
Data length per connection, max.
1 400 byte
6ES7671-0RC08-0YA0
SIMATIC WinAC RTX 2010
© Siemens AG 2014