SIEMENS
2/498
Siemens IK PI · 2015
PROFINET/Industrial Ethernet
Controllers / PC-based controllers
SIMATIC WinAC RTX
2
■
Overview
•
SIMATIC WinAC RTX:
Optimized for applications that require a high degree of
flexibility and integration capability.
•
The software solution for tasks that require hard deterministic
behavior and high performance.
•
With real-time expansion for assuring deterministic behavior
for the control section.
New with WinAC RTX 2010 SP1:
•
SIMATIC IPC427D and IPC477D are fully supported
- Communication via onboard CP 5622
- Retentive memory
- LED display of the operating status
•
Support for the new PROFIBUS CP 5612 (PCI) and CP 5622
(PCIe)
■
Benefits
•
Hard real time and maximum performance
•
Implementation of fast, S7-compatible control solutions with
low processor loading.
Alongside the control task, sufficient processor capability is
available for processing complex, demanding PC applica-
tions in parallel.
■
Technical specifications
6ES7671-0RC08-0YA0
SIMATIC WinAC RTX 2010
General information
Firmware version
V4.6
Memory
Type of memory
RAM
Work memory
• integrated (for program)
4 Mbyte; Adjustable; depends on
Non Paged Memory Pool
• integrated (for data)
4 Mbyte; Adjustable; depends on
Non Paged Memory Pool
Load memory
• integrated RAM, max.
8 Mbyte; Adjustable; depends on
Non Paged Memory Pool
CPU processing times
for bit operations, typ.
0.004 μs
for fixed point arithmetic, typ.
0.003 μs
for floating point arithmetic, typ.
0.004 μs
Reference platform
Pentium IV, 2.4 GHz
CPU-blocks
DB
• Number, max.
65 535
• Size, max.
64 kbyte
FB
• Number, max.
65 536
• Size, max.
64 kbyte
FC
• Number, max.
65 536;
Limited only by RAM set for code
OB
• Size, max.
64 kbyte
• Number of free cycle OBs
1
• Number of time alarm OBs
1
• Number of delay alarm OBs
1
• Number of time interrupt OBs
9
• Number of process alarm OBs
1
• Number of ODK OBs
3; OB 52-54
• Number of DPV1 alarm OBs
3; OB 55-57
• Number isochronous mode OBs
2; OB 61-62
• Number of startup OBs
2
• Number of asynchronous error OBs
7
• Number of synchronous error OBs
2
Nesting depth
• per priority class
24
• additional within an error OB
24
Counters, timers
and their retentivity
S7 counter
• Number
2 048
• Retentivity
- adjustable
Yes
-
lower limit
0
-
upper limit
2 047
- preset
8
• Counting range
- adjustable
Yes
-
lower limit
0
-
upper limit
999
IEC counter
• present
Yes
• Type
SFB
• Number
Unlimited
(limited only by RAM capacity)
S7 times
• Number
2 048
• Retentivity
- adjustable
Yes
-
lower limit
0
-
upper limit
2 047
• Time range
-
lower limit
10 ms
-
upper limit
9 990 s
IEC timer
• present
Yes
• Type
SFB
• Number
Unlimited
(limited only by RAM capacity)
6ES7671-0RC08-0YA0
SIMATIC WinAC RTX 2010