SIEMENS
2/493
Siemens IK PI · 2015
PROFINET/Industrial Ethernet
Controllers / Modular controllers / SIMATIC S7-400
High-availability CPUs
2
■
Technical specifications
6ES7412-5HK06-0AB0
6ES7414-5HM06-0AB0
6ES7416-5HS06-0AB0
6ES7417-5HT06-0AB0
CPU 412-5H PN/DP
CPU 414-5H PN/DP
CPU 416-5H PN/DP
CPU 417-5H PN/DP
General information
Engineering with
• Programming package
STEP 7 V 5.5 SP2 or higher
with HF1
STEP 7 V 5.5 SP2 or higher
with HF1
STEP 7 V 5.5 SP2 or higher
with HF1
STEP 7 V 5.5 SP2 or higher
with HF1
Supply voltage
24 V DC
No; Power supply
Via system power supply
No; Power supply
Via system power supply
No; Power supply
Via system power supply
No; Power supply
Via system power supply
Power losses
Power loss, typ.
7.5 W
7.5 W
7.5 W
7.5 W
Memory
Work memory
• integrated
1 Mbyte
4 Mbyte
16 Mbyte
32 Mbyte
• integrated (for program)
512 kbyte
2 Mbyte
6 Mbyte
16 Mbyte
• integrated (for data)
512 kbyte
2 Mbyte
10 Mbyte
16 Mbyte
Load memory
• expandable FEPROM, max.
64 Mbyte
64 Mbyte
64 Mbyte
64 Mbyte
• integrated RAM, max.
512 kbyte
512 kbyte
1 Mbyte
1 Mbyte
• expandable RAM, max.
64 Mbyte
64 Mbyte
64 Mbyte
64 Mbyte
CPU processing times
for bit operations, typ.
31.25 ns
18.75 ns
12.5 ns
7.5 ns
for word operations, typ.
31.25 ns
18.75 ns
12.5 ns
7.5 ns
for fixed point arithmetic, typ.
31.25 ns
18.75 ns
12.5 ns
7.5 ns
for floating point arithmetic, typ.
62.5 ns
37.5 ns
25 ns
15 ns
Counters, timers
and their retentivity
S7 counter
• Number
2 048
2 048
2 048
2 048
IEC counter
• present
Yes
Yes
Yes
Yes
S7 times
• Number
2 048
2 048
2 048
2 048
IEC timer
• present
Yes
Yes
Yes
Yes
Data areas and their retentivity
Flag
• Number, max.
8 192 byte
8 192 byte
16 384 byte
16 384 byte
Address area
I/O address area
• Inputs
8 kbyte
8 kbyte
16 kbyte
16 kbyte
• Outputs
8 kbyte
8 kbyte
16 kbyte
16 kbyte
Process image
• Inputs, adjustable
8 kbyte
8 kbyte
16 kbyte
16 kbyte
• Outputs, adjustable
8 kbyte
8 kbyte
16 kbyte
16 kbyte
Hardware configuration
Slots
• Required slots
2
2
2
2
Time of day
Clock
• Hardware clock (real-time clock)
Yes
Yes
Yes
Yes
Operating hours counter
• Number
16
16
16
16
1st interface
Interface type
integrated
integrated
integrated
integrated
Physics
RS 485 / PROFIBUS + MPI
RS 485 / PROFIBUS + MPI
RS 485 / PROFIBUS + MPI
RS 485 / PROFIBUS + MPI
Functionality
• MPI
Yes
Yes
Yes
Yes
• DP master
Yes
Yes
Yes
Yes
• DP slave
No
No
No
No
DP master
• Number of DP slaves, max.
32
32
32
32
© Siemens AG 2014