SIEMENS
2/73
Siemens IK PI · 2015
PROFINET/Industrial Ethernet
Cabling technology
Energy cables
2
■
Technical specifications
Article No.
6XV1812-8A
6XV1830-8AH10
Product-type designation
Energy Cable 2 x 0.75
Energy Cable 5 x 1.5
Product description
Energy cable (2-core), sold by the meter, not assembled
Energy cable (5-core), sold by the meter, not assembled
Acceptability for application
Connection of signaling contact and 24 V power supply to
SCALANCE X and SCALANCE W
Power supply of ET 200 modules with 7/8" power port
Cable designation
L-YY-2x1x0.75 GR
L-Y11Y-Z 5x1x1.5 GR
Electrical data
Operating voltage RMS value
600 V
600 V
Conductor cross section
of the power wires
0.75 mm²
1.5 mm²
Continuous current
of the power wires
6 A
16 A
Mechanical data
Number of electrical wires
2
5
Design of the electrical connection
FastConnect
-
No
Outer diameter
• of the inner conductor
1.3 mm
1.55 mm
• of the wire insulation
2.5 mm
2.73 mm
• of the cable sheath
7.4 mm
10.5 mm
Material
• of the wire insulation
PVC
PVC
• of the cable sheath
PVC
PUR
Symmetrical tolerance of outer diame-
ter of cable sheath
0.3 mm
0.3 mm
Color
• of the power wire insulation
Brown/blue
4x black, 1x green / yellow
• of the cable sheath
gray
gray
Bending radius
• with single bend
19 mm
27 mm
• with multiple bends
45 mm
63 mm
• with continuous bending
-
75 mm
Number of bending cycles
-
5 000 000
• Note
-
For use in cable carriers, for 5 million bending cycles
with a bending radius of 75 mm,
an acceleration of 4 m/s² and a speed of 180 m/min
Traction stress maximum
100 N
500 N
Weight per length
70 kg/km
149 kg/km
Permitted ambient conditions
Ambient temperature
• during operating
-20 … +80 °C
-40 … +80 °C
• during storage
-20 … +80 °C
-40 … +80 °C
• during transport
-20 … +80 °C
-40 … +80 °C
• during installation
-20 … +80 °C
-40 … +80 °C
Burning behaviour
Flame retardant acc. to IEC 60332-1
Flame retardant acc. to IEC 60332-1
Chemical resistance
• to mineral oil
Conditional resistance
Resistant
• to grease
Conditional resistance
Resistant
• to water
Conditional resistance
Conditional resistance
Radiological resistance to
UV radiation
Resistant
Resistant
Product properties, functions,
components
general
Product feature
• halogen-free
No
No
• silicon-free
Yes
Yes
Standards, specifications,
approvals
UL/ETL listing with 300 V rating
Yes: CL3
No
UL/ETL style with 600 V rating
Yes
Yes
Verification of suitability
• CE mark
Yes
Yes
• RoHS conformity
Yes
Yes
© Siemens AG 2014