SIEMENS
2/55
Siemens IK PI · 2015
PROFINET/Industrial Ethernet
Cabling technology
IE FC TP Cable 2 x 2
2
■
Technical specifications
Article No.
6XV1840-2AH10
6XV1841-2A
6XV1870-2B
6XV1841-2B
Product-type designation
IE FC TP Standard Cable
GP 2 x 2 (Type A)
IE FC TP Robust Standard
Cable GP 2 x 2 (Type A)
IE FC TP Flexible Cable GP
2 x 2 (Type B)
IE FC TP Robust Flexible
Cable GP 2 x 2 (Type B)
Product description
Standard bus cable (4-core),
sold by the meter,
not assembled
Standard bus cable (4-core),
sold by the meter,
not assembled
Flexible bus cable (4-core),
sold by the meter,
not assembled
Flexible bus cable (4-core),
sold by the meter,
not assembled
Acceptability for application
Standard cable with rigid
cores for fast installation
Standard cable with rigid
cores for fast installation
For occasionally moved
machine parts
For occasionally moved
machine parts
Cable designation
2YY (ST) CY 2x2x0,64/1,5-
100 GN
2YH (ST) C99Y 2x2x0,64/1,5-
100 GN
2YY (ST) CY 2x2x0,75/1,5-
100 LI GN
2YH (ST) C99Y 2x2x0,75/1,5-
100 LI GN
Electrical data
Damping ratio per length
• at 10 MHz
52 dB/km
52 dB/km
60 dB/km
60 dB/km
• at 100 MHz
195 dB/km
195 dB/km
210 dB/km
210 dB/km
Impedance for frequency range
1 MHz … 100 MHz
100
100
100
100
Relative symmetrical tolerance
of the surge impedance
at 1 MHz … 100 MHz
15 %
15 %
15 %
15 %
Near-end crosstalk per length
at 1 MHz ... 100 MHz
500 dB/km
0.5 dB/m
500 dB/km
0.5 dB/m
Transfer impedance at 10 MHz
10 m
/m
10 m
/m
20 m
/m
20 m
/m
Loop resistance per length
115
/km
115
/km
120
/km
120
/km
Insulation resistance coefficient
-
-
-
-
Operating voltage RMS value
100 V
100 V
100 V
100 V
Percentage NVP value
66 %
66 %
66 %
66 %
Mechanical data
Number of electrical wires
4
4
4
4
Design of shield
Overlapped aluminum-clad
foil, sheathed in a braided
screen of tin-plated copper
wires
Overlapped aluminum-clad
foil, sheathed in a braided
screen of tin-plated copper
wires
Overlapped aluminum-clad
foil, sheathed in a braided
screen of tin-plated copper
wires
Overlapped aluminum-clad
foil, sheathed in a braided
screen of tin-plated copper
wires
Design of the electrical connection
FastConnect
Yes
Yes
Yes
Yes
AWG number
-
-
-
-
Core diameter of the AWG22 core
0.64 mm
0.64 mm
0.75 mm
0.75 mm
Outer diameter
• of the inner conductor
0.64 mm
0.64 mm
0.75 mm
0.75 mm
• of the wire insulation
1.5 mm
1.5 mm
1.5 mm
1.5 mm
• of the inner sheath of the cable
3.9 mm
3.9 mm
3.9 mm
3.9 mm
• of the cable sheath
6.5 mm
6.5 mm
6.5 mm
6.5 mm
Symmetrical tolerance
of outer diameter of cable sheath
0.2 mm
0.2 mm
0.2 mm
0.2 mm
Material
• of the wire insulation
PE
PE
PE
PE
• of the inner sheath of the cable
PVC
FRNC
PVC
FRNC
• of the cable sheath
PVC
TPE (FR-TPE)
PVC
TPE (FR-TPE)
Color
• of the insulation of data wires
white / yellow / blue / orange
white / yellow / blue / orange
white / yellow / blue / orange
white / yellow / blue / orange
• of the cable sheath
green
green
green
green
Bending radius
• with single bend
19.5 mm
19.5 mm
32.5 mm
32.5 mm
• with multiple bends
49 mm
49 mm
52 mm
52 mm
• with continuous bending
-
-
-
-
Number of bending cycles
-
-
-
-
• Note
-
-
-
-
Number of torsion cycles with torsion
by ± 180° on 1 m cable length
-
-
-
-
Traction stress maximum
150 N
150 N
150 N
150 N
Weight per length
67 kg/km
67 kg/km
68 kg/km
68 kg/km
© Siemens AG 2014