PROFINET/Industrial Ethernet
Industrial Ethernet Switches
SCALANCE X-300 managed
2
Network management
The network management provides the following functions:
•
Password-protected dial-up for "Administrator" (read and write
authorization) and "User" (read only)
•
Read-out of version and status information
•
Setting the signal and standby mask and address information
•
Fixed parameterization of the ports
(data rates, half/full duplex)
•
Setting parameters of the VLANs and multicast services
•
Parameterization of the standby connections for a redundant
ring link
•
Setting of Rapid Spanning Tree parameters
•
Parameterization of the web management services
• Security
- Ports can be connected or disconnected
- Authentication in accordance with IEEE 802.1x
- Support from Access Control List (ACL)
•
Parameterization of user administration of SNMP V1, V2c, V3
•
Output of statistics information
•
Diagnosis of data traffic by means of a parameterizable mirror
port with a standard commercial network analyzer
•
Loading of new firmware versions or of the configuration data
via the network by a TFTP server or directly via HTTP/HTTPS
using a Web browser
•
Saving the configuration data or log table via the network on a
TFTP server
If faults occur in the network, the SCALANCE X-300 switch can
independently send error messages (traps) to a network man-
agement system or also e-mails to a predefined network admin-
istrator.
Remote monitoring (RMON) provides the following functions:
The SCALANCE X-300 switch can collect statistics information
according to the RMON groups 1 through 4. These include, for
example, fault statistics that are kept for each port. This informa-
tion can be read out through web-based management in the sta-
tistics sub-area.
■
Technical specifications
Article No.
6GK5304-2BD00-2AA3
6GK5306-1BF00-2AA3
6GK5307-3BL00-2AA3
6GK5307-3BM00-2AA3
Product-type designation
SCALANCE X304-2FE
SCALANCE X306-1LD FE
SCALANCE X307-3
SCALANCE X307-3LD
Transmission rate
Transfer rate 1
10 Mbit/s
10 Mbit/s
10 Mbit/s
10 Mbit/s
Transfer rate 2
100 Mbit/s
100 Mbit/s
100 Mbit/s
100 Mbit/s
Transfer rate 3
-
-
1 000 Mbit/s
1 000 Mbit/s
Interfaces
Number of electrical/optical
connections for network components
or terminal equipment maximum
6
7
10
10
Number of electrical connections
• for network components
and terminal equipment
4
6
7
7
• for operator console
-
-
-
-
• for signaling contact
1
1
1
1
• for media module
-
-
-
-
• for power supply
1
1
1
1
• for redundant power supply
2
2
2
2
Design of electrical connection
• for network components
and terminal equipment
RJ45 port
RJ45 port
RJ45 port
RJ45 port
• for operator console
-
-
-
-
• for signaling contact
2-pole terminal block
2-pole terminal block
2-pole terminal block
2-pole terminal block
• for power supply
4-pole terminal block
4-pole terminal block
4-pole terminal block
4-pole terminal block
Number of optical interfaces
for optical waveguide
• at 100 Mbit/s
2
1
-
-
• at 1 000 Mbit/s
-
-
3
3
© Siemens AG 2014