Technical specifications
(continued)
Drive systems
SIMOTRAS HD AC power controller
Product designation
SIMOTRAS HD AC power controller
Type
6SG7070-
0EB60-0
6SG7072-
0EB60-0
6SG7076-
0EB60-0
6SG7080-
0EB60-0
6SG7082-
0EB60-0
6SG7085-
0EB60-0
110 ... 500 V 3 AC, 225 ... 900 A
Rated supply voltage
Power unit
V
110 -10 % ... 500 + 10 % 3 AC
Rated frequency
Hz
50/60
The devices automatically adjust to the frequency of the applied line
voltage in a range from 45 ... 65 Hz.
Rated current
A
225
285
360
525
680
900
Rated supply voltage
Electronic power supply
V
380 (-25 %) ... 460 (+15 %) 2 AC
I
rated
= 1 A
or 190 (-25 %) ... 230 (+15 %) 1 AC
I
rated
= 2 A
(-35 % for 1 min.)
Phase fuse
1)
3 units
A/V
3NE1227-0
250/690
3NE1331-0
350/690
3NE1332-0
400/690
3NE1435-0
560/690
3NE3340-8
900/690
6RY1702-
0BA01
2) '
1250/660
Rated supply voltage
Fan
V
400 (± 15 %) 3 AC 50 Hz
460 (± 10 %) 3 AC 60 Hz
400 (± 10 %) 3 AC 50 Hz
460 (± 10 %) 3 AC 60 Hz
Rated current
Fan
A
0.24
1.1
Overload possibility
3)
20 s duration:
I
= 2 ×
I
rated
then 70 s duration:
I
=
I
rated
then 60 s duration:
I
= 0 A
(cycle duration 150 s)
Power loss for rated current,
approx.
W
839
1020
1300
1827
2890
3550
Minimum load
A
10
10
10
15
15
15
Ambient temperature during ope-
ration at rated current
°C
0 ... 40
forced ventilation
Upper limit temperature with cur-
rent derating
°C
50
Cooling air requirement
m
3
/h
570
1400
2400
Sound pressure level
L
pA
(1 m)
dB
73
88
Storage and transport temperature
°C
-25 ... +70
Installation altitude above sea level
m
≤
1000 at rated current
max. 3500 with reduced voltage and current
Environmental class
DIN IEC 60721-3-3
3K3
Degree of protection
DIN EN 60529
IP00
IP00
IP00
IP00
IP00
IP00
D400 device type
225 Mre
285 Mre
360 Mre
525 Mre
680 Mre
900 Mre
Dimensions
See dimensional drawings
Weight, approx.
kg
30
30
30
45
85
137
1)
The fuses listed are not included with the device. The fuses listed are
recommended fuses that must be ordered separately.
2)
Fuses included with device. No semiconductor fuses are necessary.
3)
It is permissible to operate the device without interruption with the rated
connection current
I
rated
. This will cause the thyristors to reach their limit
temperature. It is not possible to accelerate, i.e. increase the current from
this operating state.