LENZE
Mains filter B, C1 up to 50 m
Mains filter B is used to operate 9300 controllers on public
supply networks or in industrial areas. With mains filter B, EN
ƒ
The filters are designed as add-on filters.
ƒ
The motor cable lengths stated are maximum values and
depend on inverter type and switching frequency
61800-3categoryC1upto50mmotorcablelengthiscomplied
with .
ƒ
The following assignment applies to operation with rated
power.
Mains filter B data
Product key
Mains
voltage
Motor power
Mass
Dimensions
Max. cable
length C1
Rated current
Mains filter
Inverter
(asynchronous
motor, 4-pole)
m
[kg]
H x B x T
[mm]
l
[m]
I
[A]
U
Netz
[V]
P
N
[kW]
2.5
150 x 78 x 230
50
1.5
EZN3B2400H002
EVF9321-EV
3 AC
400/480
0.37
3
2.5
EZN3B1500H003
EVF9322-EV
0.75
3.1
4
EZN3B0900H004
EVF9323-EV
1.5
4.6
180 x 97 x 230
7
EZN3B0500H007
EVF9324-EV
3
11.8
260 x 135 x 230
13
EZN3B0300H013
EVF9325-EV
5.5
12.1
24
EZN3B0150H024
EVF9326-EV
11
Data sheet for mains filter for operating with increased
rated power
DS_ZB_EZN_0002
Data sheet on mains filters
DS_ZB_EZN_0001
Available for download at
Available for download at
Mains filter, C1 up to 10 m and C2 up to 50 m
The mains filter is used for inverters with a 15 … 90kW power
in order to operate with up to a 50m motor cable length in
ƒ
The filters are designed as footprint filters.
ƒ
Built-on mains filters are also available (category C1 with
50m of shielded motor cable)
industrial areas or with up to a 10m motor cable length on
public networks. Mains filters correspond to category C1 EN
ƒ
When mounting the inverter in cold plate technology, only
built-on mains filters can be used for interference suppres-
sion.
61800-3 up to 10m motor cable length and category C2 EN
61800-3 up to 50m motor cable length.
ƒ
The motor cable lengths stated are maximum values and
depend on the inverter type and switching frequency.
ƒ
The following assignment applies to operation with rated
power.
Mains filter data
Product key
Mains
voltage
Motor power
Mass
Dimensions
Rated current
Mains filter
Inverter
(asynchronous mo-
tor, 4-pole)
m
[kg]
H x B x T
[mm]
I
N
[A]
U
Netz
[V]
P
N
[kW]
13
410 x 236 x 110
42
E82ZN22334B230
EVF9327-EV
3 AC
400/480
15
EVF9328-EV
22
19
55
E82ZN30334B230
EVF9329-EV
30
26
580 x 318 x 114
80
E82ZN45334B230
EVF9330-EV
45
29
685 x 318 x 114
100
E82ZN55334B230
EVF9331-EV
55
53
760 x 428 x 114
135
E82ZN75334B230
EVF9332-EV
75
90
765 x 428 x 114
165
E82ZN90334B230
EVF9333-EV
90
Data sheet on mains filters E82ZN
DS_ZB_E82ZN_0001
Available for download at
Frequency inverter en 02/2009
†
78
9300 vector frequency inverter
Accessories