LENZE
Mains filter
Furthermore, a mains filter achieves the efficiency of a mains
choke which also reduces the r.m.s. value of the mains current.
Mains filters are available in a power range of 15 … 90 kW.
A mains filter is a mains choke and RFI filter combination in
a housing. It is used to comply with category C1 (with 10m of
shielded motor cable) and C2 (with 50m of shielded motor
cable) according to EN 61800-3.
ƒ
Important: Only use the mains filter in combination with
E82EV
☐☐☐
K4B2
☐
1 type 8200 vectors! The 8200 vector
frequencyinverterisalsoavailablewithafullyfittedmains
filter (types: E82EV
☐☐☐
K4B3
☐☐
).
ƒ
The filters are designed as footprint filters.
ƒ
Built-on mains filters are also available (category C1 with
50m of shielded motor cable)
ƒ
When mounting the inverter in cold plate technology, only
built-on mains filters can be used for interference suppres-
sion.
ƒ
The motor cable lengths stated are maximum values and
depend on the inverter type and switching frequency.
ƒ
The following assignment applies to operation with rated
power.
Mains filter data
Product key
Mains
voltage
Motor power
Mass
Dimensions
Rated current
Mains filter
Inverter
(asynchronous mo-
tor, 4-pole)
m
[kg]
H x B x T
[mm]
I
N
[A]
U
Netz
[V]
P
N
[kW]
13
410 x 236 x 110
42
E82ZN22334B230
E82EV153K4B201
3 AC
400/500
15
E82EV223K4B201
22
19
55
E82ZN30334B230
E82EV303K4B201
30
26
580 x 318 x 114
80
E82ZN45334B230
E82EV453K4B201
45
29
685 x 318 x 114
100
E82ZN55334B230
E82EV553K4B201
55
53
760 x 428 x 114
135
E82ZN75334B230
E82EV753K4B201
75
90
765 x 428 x 114
165
E82ZN90334B230
E82EV903K4B201
90
Assignment of built-on mains filter
DS_ZB_EZN_0002
Available for download at
Data sheet on mains filters
DS_ZB_EZN_0001
Available for download at
Data sheet for mains filter for operating with increased
rated power
DS_ZB_EZN_0003
Available for download at
51
†
Frequency inverter en 02/2009
8200 vector frequency inverter
Accessories