LENZE
Rated data
Other rated data, e.g. for operating with increased rated
power
DS_GD_8200v_0001
ƒ
The data is valid for operation at 1/N/PE (3/PE) AC 230 V
or DC 325 V.
ƒ
Unless otherwise specified, the data refers to the default
setting with a switching frequency of 8 kHz.
Available for download at
Motor power
2.2
1.5
0.75
0.55
P
N
[kW]
(asynchronous motor, 4-pole)
Product key
E82EV222K2C
E82EV152K2C
E82EV751K2C
E82EV551K2C
Filter integrated
2)
E82EV222K2C200
E82EV152K2C200
E82EV751K2C200
E82EV551K2C200
No filter
Mains voltage range
1/N/PE AC 180 V -0% … 264 V +0%; 45 Hz -0% … 65 Hz +0%
U
Netz
[V]
3/PE AC 100 V -0% … 264 V +0%; 45 Hz -0% ... 65 Hz +0%
Alternative DC supply
DC 140 V - 0 % ... 370 V + 0 %
U
DC
[V]
Rated mains current
4)
15
9
6
I
Netz
[A]
Without mains choke 1/N/PE
18
12.5
7.5
5.6
I
Netz
[A]
With mains choke 1/N/PE
4)
9.1
5.2
3.9
I
Netz
[A]
Without mains choke 3/PE
9
6.3
3.6
2.7
I
Netz
[A]
With mains choke 3/PE
Rated output current
9.5
7
4
3
I
N
[A]
8 kHz
Max. output current
14.2
10.5
6
4.5
I
max
[A]
8 kHz
1)
Brake chopper data
47
90
R
[Ohm]
Min. brake resistance
Power loss
130
100
60
50
P
V
[W]
Dimensions
240
180
H
[mm]
Height
60
B
[mm]
Width
140
T
[mm]
Depth
Mass
1.6
1.2
m
[kg]
Permissible motor cable length
50
l
[m]
Shielded
3)
100
l
[m]
Unshielded
3)
60 s
1)
Max. 20 m motor cable (shielded) for category C2 according to EN 61800-3
(motor cable length for category C1 depends on inverter type and switching
frequency)
2)
Permissible cable length may be affected if EMC conditions have to be met.
3)
Operation only permitted with mains choke
4)
Dimensioned drawings
DS_MB_8200v_0001
Available for download at
39
†
Frequency inverter en 02/2009
8200 vector frequency inverter
Inverter