BALDOR
235
Inverter/Vector Motors & Controls
Farm Duty
Motors
Definite Purpose
Motors
Unit Handling
Motors
Brake Motors
200 & 575 Volt
Motors
IEC Frame
Motors
50 Hertz
Motors
Inverter/Vector
Motors & Controls
DC Motors
and Controls
Soft Starters &
Dynamic Brakes
Hp
kW
±nput
Voltage
Rated
Amps
±nduct.
(mH)
Full Load
Watts
Loss
Catalog
Number
LIst
PrIce
Mult.
Sym.
Ap’x.
Shpg.
Wgt.
OptIonal NEMA 1
CabInet Enclosure
(a)
208/230 Volt Input, 60 Hz, 3% ±mpedance
1
0.75
230
4
3
15
LRAC00401
316
E8
9
LRENC-8
1 1/2-2
1.15-1.5
208/230
8
1.5
20
LRAC00801
316
E8
3
LRENC-8
3
2.2
208/230
12
1.25
26
LRAC01201
510
E8
10
LRENC-8
5
3.7
208/230
18
0.8
36
LRAC01801
535
E8
4
LRENC-8
7 1/2
5.5
208/230
25
0.5
48
LRAC02501
642
E8
11
LRENC-13
10
7.4
208/230
35
0.4
49
LRAC03501
681
E8
19
LRENC-13
15
11.1
230
45
0.3
54
LRAC04501
718
E8
23
LRENC-13
20
14.9
230
55
0.25
64
LRAC05501
763
E8
25
LRENC-13
25
18.6
208/230
80
0.2
82
LRAC08001
803
E8
25
LRENC-13
30-40
22.3-29.8
208/230
130
0.1
108
LRAC13001
977
E8
29
LRENC-13
50
37.2
208/230
160
0.075
116
LRAC16001
1,135
E8
41
LRENC-13
460 Volt Input, 60 Hz, 3% ±mpedance
1-1 1/2
0.75-1.1
460
2
12
8
LRAC00201
266
E8
4
LRENC-8
2
1.5
460
4
6.5
20
LRAC00402
335
E8
4
LRENC-8
3-5
2.2-3.7
460
8
3
29
LRAC00802
391
E8
7
LRENC-8
7 1/2
5.5
460
12
2.5
31
LRAC01202
539
E8
9
LRENC-8
10
7.4
460
18
1.5
43
LRAC01802
564
E8
10
LRENC-8
15
11.1
460
25
1.2
52
LRAC02502
807
ED
13
LRENC-13
20-25
14.9-18.6
460
35
0.8
54
LRAC03502
858
ED
15
LRENC-13
30
22.3
460
45
0.7
62
LRAC04502
1,024
E8
27
LRENC-13
40
29.8
460
55
0.5
67
LRAC05502
1,057
ED
29
LRENC-13
50-60
37.2-44.7
460
80
0.4
86
LRAC08002
1,069
E8
33
LRENC-13
75-100
56-75
460
130
0.2
180
LRAC13002
1,087
E8
43
LRENC-13
125
93.2
460
160
0.15
149
LRAC16002
1,198
E8
50
LRENC-13
150
112
460
200
0.11
168
LRAC20002
1,664
E8
54
LRENC-13
200
149
460
250
0.09
231
LRAC25002
2,170
E8
80
LRENC-17
250-300
186.5-223.8
460
400
0.06
333
LRAC40002
2,785
E8
118
LRENC-17
350-400
261-298
460
500
0.05
340
LRAC50002
3,910
E8
118
LRENC-26C
500
373
460
600
0.04
414
LRAC60002
6,091
E8
175
LRENC-26C
575 Volt Input, 60 Hz, 3% ±mpedance
1-2
0.75-1.5
575
2
20
12
LRAC00202
295
E8
4
LRENC-8
3
2.2
575
4
9
20
LRAC00403
349
E8
4
LRENC-8
5
3.7
575
8
3
29
LRAC00802
391
E8
7
LRENC-8
7 1/2
5.5
575
8
5
26
LRAC00803
516
E8
10
LRENC-8
10
7.5
575
12
2.5
31
LRAC01202
539
E8
9
LRENC-8
15
11
575
18
1.5
43
LRAC01802
564
E8
10
LRENC-8
20
15
575
25
1.2
52
LRAC02502
807
ED
13
LRENC-13
30
22
575
35
0.8
54
LRAC03502
858
ED
15
LRENC-13
40
30
575
45
0.7
62
LRAC04502
1,024
E8
27
LRENC-13
50
37.2
575
55
0.5
67
LRAC05502
1,057
ED
29
LRENC-13
60-75
44.7-56
575
80
0.4
86
LRAC08002
1,069
E8
33
LRENC-13
100-125
75-93
575
130
0.2
180
LRAC13002
1,087
E8
43
LRENC-13
150
112
575
160
0.15
149
LRAC16002
1,198
E8
50
LRENC-13
200
149
575
200
0.11
168
LRAC20002
1,664
E8
54
LRENC-13
250
186.5
575
250
0.09
231
LRAC25002
2,170
E8
80
LRENC-17
300
223/8
575
320
0.075
264
LRAC32002
2,614
E8
102
LRENC-17
1 thru 500 Hp
Applications:
²ine side power conditioning for AC motor controls
to prevent unwanted harmonics and nuisance drive trips. ²oad side
power conditioning to smooth power wave form to connected motor
to reduce motor electrical stresses and increase motor life.
Features:
Open construction with connection terminals.
3% impedance rating at rated current.
Three Phase - Line
and Load Reactors
(a)
See page 236 for ²ine Reactor enclosures, prices and dimensions
NOTE:
2.5% impedance rating. % impedance decreases if load current is less than reactor rated current.