BALDOR
223
Inverter/Vector Motors & Controls
Farm Duty
Motors
Definite Purpose
Motors
Unit Handling
Motors
Brake Motors
200 & 575 Volt
Motors
IEC Frame
Motors
50 Hertz
Motors
Inverter/Vector
Motors & Controls
DC Motors
and Controls
Soft Starters &
Dynamic Brakes
Applications:
Constant torque, variable torque or constant horsepower
applications. New installations, replacements and original equipment
manufacturers (OEM).
Features:
NEMA 1 and NEMA 4 enclosure. Output frequency 0 to
500 Hz with peak overload capacity of 175%. Separate accel/decel
rates and controlled reversing. Built-in two and three input P±D process
control loop.
1 thru 3 Hp
1 thru 60 Hp
1 thru 500 Hp
1 thru 300 Hp
115/230 VAC
230 VAC
460 VAC
600 VAC
1 Phase - 50/60 Hz
3 Phase - 50/60 Hz
3 Phase - 50/60 Hz
3 Phase - 50/60 Hz
VS1SP Inverter/Encoderless
Vector Drive
±nput RatIngs
Voltage
115
230
230
460
600
Voltage Range
95-130
180-264
180-264
340-528
515-660
Phase
Single Phase
Three Phase (single phase with derating)
Frequency
50/60Hz +5%
Impedance
1% minimum from mains connection
Output RatIngs
Horsepower
1-3 Hp @ 115/230VAC, 1PH; 1-60 Hp @ 230VAC, 3PH; 1-1000 Hp @ 460VAC, 3PH; 1-300 Hp @ 575VAC, 3PH
Overload Capacity
Heavy Duty (Constant Torque) = 150% for 60 seconds, 175% for 3 seconds
Normal Duty (Variable Torque) = 115% for 60 seconds
Frequency
0-500Hz
Voltage
0 to maximum input voltage (RMS) (Note: 0 to 230 V for 115 V Single Phase Units)
ProtectIve
Features
Trip
Missing control power, over current, over voltage, under voltage, over temperature (motor or control), output shorted or
grounded, motor overload
Stall Prevention
Over voltage suppression, overcurrent suppression
External Output
LED trip condition indicators, 4 assignable logic outputs, 2 assignable analog outputs
Short Circuit
Phase to phase, phase to ground
Electronic Motor Overload
Meets UL508C (I
2
T)
EnvIronmental
CondItIons
Temperature
-10 to 45°C. Derate 3% per °C to maximum ambient temperature of 55°C.
(NEMA 4X B-Frame -10-40°C)
Cooling
Forced air
Enclosure
NEMA 1
NEMA 4X
Altitude
Sea level to 3300 Feet (1000 Meters) Derate 2% per 1000 Feet (303 Meters) above 3300 Feet
Humidity
NEMA 1:
10 to 90% RH Non-Condensing
NEMA 4X:
To 100% RH Condensing
Shock / Vibration
1G / 0.5G at 10Hz to 60Hz
Storage Temperature
-10 to +65°C
Keypad DIsplay
Display
LCD Graphical 128x64 Pixel
Keys
14 key membrane with tactile feedback
Functions
Output status monitoring, Digital speed control, Parameter setting and display, Diagnostic and Fault log display, Motor run
and jog, Local/Remote toggle
LED Indicators
Forward run command, Reverse run command, Stop command, Jog active
Remote Mount
200 feet (60.6m) maximum from control, NEMA 4 Rated
Trip
Separate message and trace log for each trip, last 10 trips retained in memory
Control
Specifications
Control Method
Microprocessor controlled PWM output, selectable encoderless vector or V/Hz inverter
PWM Frequency
Adjustable 1.5-5kHz STD, 5-16 kHz quiet
Frequency Setting
³5 VDC, 0-5 VDC ³10 VDC, 0-10 VDC, 4-20 mA or 0-20 mA; digital (keypad), Serial Comms/USB 2.0, and Modbus RTU
standard
Accel/Decel
0-3600 seconds
V/Hz Ratio
Linear to squared reduced, base frequency, output voltage, minimum frequency limit, maximum frequency limit
Torque Boost
0-30% of input voltage; automatic with manual override
Brake Torque
20% standard on Sizes AA and B, 1% standard on Size C, D; External on E, F, G-Frames
Skip Frequency
Three zones 0-Max frequency
PC Setup Software
MINT® WorkBench Software available using the USB 2.0 port for commissioning wizard, ±rmware download, parameter
viewer, scope capture and cloning
Maximum Output Frequency
500 Hz
Selectable Operating Modes
Keypad, Standard Run 2-Wire, Standard Run 3-Wire, 15 Preset Speeds, Fan Pump 2-Wire, Fan Pump 3-Wire, Process
Control, 3-SPD ANA 2-Wire, 3-SPD ANA 3-Wire, Electronic Pot 2-Wire, Electronic Pot 3-Wire, Network Pro±le Run, Bipolar
Analog Inputs
One Differential
³5VDC, ³10VDC, 4-20 mA and 0-20 mA, 11-bit + sign
One Single Ended
0 - 10 VDC, 11-bit
Input Impedance
80 kOhms (Volt mode); 500 Ohms (Current mode)
Analog Outputs
Analog Outputs
2 Assignable
Full Scale Range
AOUT1 (0-5V, 0-10V, 0-20mA or 4-20mA), AOUT2 (+5V, +10V)
Source Current
1 mA maximum (volt mode), 20mA (current mode)
Resolution
9 bits
Digital Inputs
Opto-isolated Inputs
8 Assignable, 1 dedicated input (Drive Enable)
Rated Voltage
10 - 30 VDC (closed contacts std)
Input Impedance
4.71 k Ohms
Leakage Current
10 mA maximum
Update Rate
16 msec
Digital Outputs
(2 Opto Outputs)
Rated Voltage
5 to 30VDC
Maximum Current
60 mA Maximum
ON Voltage Drop
2 VDC Maximum
OFF Leakage Current
0.1 mA Maximum
Output Conditions
31 Conditions
Digital Outputs
(2 Relay Outputs)
Rated Voltage
5 to 30VDC or 240VAC
Maximum Current
5A Maximum non-inductive
Output Conditions
31 Conditions