![](https://www.globalindustrialsupplies.eu/wp-content/uploads/2016/09/baldor-gallery-5-200x200.jpg)
178
Inverter/Vector Motors & Controls
Farm Duty
Motors
Definite Purpose
Motors
Unit Handling Motors
Brake Motors
200 & 575 Volt
Motors
IEC Frame
Motors
50 Hertz
Motors
Inverter/Vector
Motors & Controls
DC Motors
and Controls
Soft Start & Dynamic
Brakes
10 Hp
230 VAC
3 Phase - 50/60 Hz
10 thru 200 Hp
460 VAC
3 Phase - 50/60 Hz
Applications:
Constant or Variable Torque Applications. New installations and
original equipment manufactures (OEM).
Features:
Exclusively for use with our RPMAC ±nterior Permanent Magnet
Motors. Very high efficiency motor/drive packages. NEMA 1 Enclosures. Output
frequency 0 to 66 Hz with peak overload capacity of 175%. Built-in two and three
input P±D process control loop. Automatically tuned to Baldor RPMAC ±nterior PM
Motors. Uses same Graphic Keypad and Expansion Boards as the VS1SP/GV
Families.
VS1PM Permanent
Magnet Drive
Output
RatIngs
Horsepower
10 HP @ 230VAC, 3PH; 10-200 HP @ 460VAC, 3PH
Overload Capacity
Heavy Duty (Constant Torque) = 150% for 60 seconds, 175% for 3 seconds
Normal Duty (Variable Torque) = 115% for 60 seconds
Frequency
0-66 Hz
Voltage
0-Maximum input voltage (RMS)
±nput
RatIngs
Frequency
50 or 60 Hz
³5%
Voltage
230 = 180-234 & 460 = 340-528
Phase
Three Phase (single phase with derating)
Impedance
1% minimum from mains connection
Control
Spec
Control Method
Microprocessor controlled PWM, selectable closed loop vector
PWM Frequency
Adjustable 4-5 kHz STD, 5-16 kHz quiet
Speed Setting
³5 VDC, 0-5 VDC ³10 VDC, 0-10 VDC, 4-20 mA or 0-20 mA; digital (keypad), Serial Comms/USB 2.0, and Modbus RTU
Accel/Decel
0-3600 sec
Brake Torque
20% standard on Sizes AA and B, 1% standard on Size C, D, E requires external resistor
Motor Matching
Automatic tuning to motor with manual override
PC Setup Software
Mint WorkBench Software available using the USB 2.0 port for commissioning wizard, firmware download, parameter viewer scope capture and
cloning,
Maximum Output Frequency
66 Hz
Selectable Operating Modes
Keypad, Standard Run, 2-Wire, Standard Run 3-Wire, 15 Preset Speeds, Fan Pump 2-Wire, Fan Pump 3-Wire, Process Control, 3-SPD ANA
2-Wire, 3-SPD ANA 3-Wire, Electronic Pot 2-Wire, Electronic Pot 3-Wire, Network Profile Run, Bipolar
Motor Feedback
Feedback Type
Resolver Feedback (Std.);
Optional Incremental Encoder Feedback for VT Loads.
ProtectIve
FunctIons
Trip
Missing control power, over current, over voltage, under voltage, over temperature (motor or control), output shorted or grounded, motor
overload, encoder loss.
Stall Prevention
Over voltage suppression, overcurrent suppression
External Output
LED trip condition indicators, 4 assignable logic outputs, 2 assignable analog outputs
Short Circuit
Phase to phase, phase to ground
Electronic Motor Overload
Meets UL508C (I
2
T)
EnvIronmental
CondItIons
Temperature
10 to 45°C. Derate 3% per °C to maximum ambient temperature of 55°C.
Cooling
Forced air
Enclosure
NEMA 1 (-1B, -1T)
Altitude
Sea level to 3300 Feet (1000 Meters) Derate 2% per 1000 Feet (303 Meters) above 3300 Feet
Humidity
NEMA 1:
10 to 90% RH Non-Condensing
Shock/Vibration
1G / 0.5G at 10Hz to 60Hz
Storage Temperature
-10 to +65°C
Keypad
DIsplay
Display
LCD Graphical 128x64 Pixel
Keys
14 key membrane with tactile feedback
Functions
Output status monitoring, Digital speed control, Parameter setting and display, Diagnostic and Fault log display, Motor run and jog, Local/
Remote toggle, One-step tuning
LED Indicators
Forward run command, Reverse run command, Stop command, Jog active
Remote Mount
200 feet (60.6m) maximum from control, NEMA 4 Rated
Trip
Separate message and trace log for each trip, last 10 trips retained in memory
Analog ±nputs
One Differential
³5VDC, ³10VDC, 4-20 mA and 0-20 mA, 11-bit + sign
One Single Ended
0 - 10 VDC, 11-bit
Input Impedence
80 kOhms (Volt mode); 500 Ohms (Current mode)
Analog Outputs
Analog Outputs
2 Assignable
Full Scale Range
AOUT1 (0-5V, 0-10V, 0-20mA or 4-20mA), AOUT2 (+5V, +10V)
Source Current
1 mA maximum (volt mode), 20mA (current mode)
Resolution
9 bits
DIgItal ±nputs
Opto-isolated Inputs
8 Assignable, 1 dedicated input (Drive Enable)
Rated Voltage
10 - 30 VDC (closed contacts std)
Input Impedance
4.71 k Ohms
Leakage Current
10 mA maximum
Update Rate
16 msec
DIgItal Outputs
(2 Opto Outputs)
Rated Voltage
5 to 30VDC
Maximum Current
60 mA Maximum
ON Voltage Drop
2 VDC Maximum
OFF Leakage Current
0.1 mA Maximum
Output Conditions
31 Conditions
DIgItal Outputs
(2 Relay Outputs)
Rated Voltage
5 to 30VDC or 240VAC
Maximum Current
5A Maximum non-inductive
Output Conditions
31 Conditions