ABB
ABB/ BU Machines / HV Induction motors IEC catalogue / Engineered motors EN 12-2007
87
2
Efficiency
Power factor
Current
Torque
Sound
Full
3/4
Full
3/4
I
N
I
S
I
0
T
N
T
S
T
max
Rotor
Motor
pressure
Output
Motor
Product
Speed
load
load
load
load
inertia
weight
level L
P
kW
type
ID
r/min
100%
75%
100% 75%
A
I
N
A
Nm
T
N
T
N
kgm
2
kg
dB(A)
HV Modular motors
Technical data for totally enclosed squirrel
cage three phase motors
IP 55 - IC 611 - Insulation class F, temperature rise class B
10000 V - 50 Hz
1000 r/min = 6 poles
10000 V 50 Hz
450
AMA 450L6A
8613
992
95.0
94.5
0.81
0.76
34
6.5
15
4331
1.0
2.7
30.6
4070
79
500
AMA 450L6A
8614
991
95.0
94.8
0.83
0.78
37
5.9
15
4816
0.9
2.4
30.6
4070
79
560
AMA 450L6A
8615
990
95.1
95.0
0.84
0.80
41
5.4
15
5401
0.8
2.2
30.6
4070
79
630
AMA 450L6A
8616
989
95.0
95.1
0.85
0.82
45
5.0
15
6084
0.8
2.0
30.8
4070
79
710
AMA 450L6A
8617
989
95.3
95.3
0.84
0.81
51
5.3
18
6852
0.8
2.1
32.3
4200
79
800
AMA 450L6A
8618
989
95.4
95.5
0.85
0.83
57
4.9
19
7721
0.7
1.9
32.6
4200
79
900
AMA 500L6A
221
994
95.6
95.7
0.87
0.84
63
5.6
21
8649
0.6
2.1
64.0
5210
79
1000
AMA 500L6A
222
994
95.8
95.8
0.86
0.84
70
5.6
23
9609
0.6
2.1
67.5
5350
79
1120
AMA 500L6A
223
994
95.9
96.0
0.86
0.82
79
5.6
28
10760
0.6
2.1
70.9
5500
79
1250
AMA 500L6A
500
994
96.1
96.1
0.85
0.82
88
5.6
31
12009
0.6
2.1
74.6
5660
79
1400
AMA 500L6A
501
993
96.1
96.2
0.88
0.85
96
6.0
30
13460
0.8
2.2
75.8
5670
79
750 r/min = 8 poles
10000 V 50 Hz
630
AMA 500L8A
8619
744
95.3
95.3
0.83
0.78
46
6.0
19
8082
1.0
2.1
74.4
5180
77
710
AMA 500L8A
225
746
95.7
95.6
0.82
0.77
52
5.7
22
9094
0.7
2.2
79.3
5330
77
800
AMA 500L8A
226
745
95.8
95.8
0.82
0.78
59
5.7
25
10248
0.7
2.2
83.7
5480
77
900
AMA 500L8A
227
745
95.9
95.9
0.82
0.77
66
5.7
28
11529
0.7
2.2
88.1
5620
77
1000
AMA 500L8A
502
745
96.0
96.1
0.83
0.78
73
5.7
30
12810
0.7
2.2
96.9
5920
77
1120
AMA 500L8A
503
745
96.0
96.1
0.84
0.81
80
5.6
30
14359
0.8
2.0
97.6
5920
77
600 r/min = 10 poles
10000 V 50 Hz
450
AMA 500L10A
228
595
94.4
94.4
0.81
0.75
34
5.8
16
7223
0.9
2.4
70.6
5000
76
500
AMA 500L10A
229
595
94.6
94.6
0.82
0.77
37
5.9
17
8028
0.9
2.4
75.3
5150
76
560
AMA 500L10A
230
595
94.8
94.9
0.82
0.77
42
5.9
19
8983
0.9
2.4
80.5
5300
76
630
AMA 500L10A
231
595
95.0
95.0
0.82
0.77
47
5.9
21
10107
0.9
2.4
85.0
5450
76
710
AMA 500L10A
504
595
95.1
95.1
0.82
0.77
53
5.9
24
11391
0.9
2.4
89.5
5600
76
500 r/min = 12 poles
10000 V 50 Hz
315
AMA 500L12A
8629
495
93.3
93.2
0.74
0.67
26
4.5
15
6077
0.6
2.2
57.7
4860
76
355
AMA 500L12A
8630
495
93.6
93.4
0.73
0.66
30
4.6
17
6847
0.7
2.2
61.4
5010
76
400
AMA 500L12A
8631
495
94.0
93.8
0.74
0.67
33
4.7
18
7714
0.7
2.2
68.8
5300
76
450
AMA 500L12A
235
495
94.0
93.9
0.76
0.70
36
5.3
19
8678
0.8
2.3
84.2
5430
76
500
AMA 500L12A
236
495
94.2
94.1
0.76
0.70
40
5.2
21
9644
0.8
2.3
88.7
5570
76
560
AMA 500L12A
507
495
94.3
94.2
0.76
0.70
45
5.2
24
10802
0.8
2.3
93.1
5720
76
Data presented in rating lists are typical values.
Guaranteed values on request. All engineered motors
are optimized for the specified application. Accurate
motor data will be given on request at quotation phase.
Legally binding performance and specification data is
given to the end user once each order is confirmed.