HV Modular motors
Technical data for totally enclosed squirrel
cage three phase motors
IP 55 - IC 81W - Insulation class F, temperature rise class B
6000 V - 50 Hz
1000 r/min = 6 poles
6000 V 50 Hz
500
AMA 400L6L
8642
986
94.9
95.4
0.84
0.82
60
4.3
19
4842
0.6
1.7
13.7
2830
77
560
AMA 400L6L
25
987
95.0
95.4
0.84
0.81
68
5.0
25
5416
0.8
2.0
16.7
2810
77
630
AMA 400L6L
26
987
95.1
95.5
0.85
0.82
75
4.9
25
6096
0.8
1.9
18.0
2910
77
710
AMA 400L6L
27
988
95.4
95.7
0.85
0.82
85
5.3
30
6861
0.9
2.1
20.4
3100
77
800
AMA 400L6L
28
988
95.5
95.8
0.84
0.81
96
5.4
35
7730
0.9
2.1
21.6
3190
77
900
AMA 450L6L
29
991
95.8
96.1
0.86
0.83
106
5.3
35
8674
0.7
2.1
35.5
3830
78
1000
AMA 450L6L
30
990
96.0
96.4
0.87
0.85
115
5.1
34
9643
0.7
1.9
37.8
3950
78
1120
AMA 450L6L
31
991
96.2
96.5
0.86
0.84
130
5.3
40
10796
0.7
2.0
40.0
4080
78
1250
AMA 450L6L
32
990
96.1
96.5
0.87
0.85
144
5.0
40
12059
0.7
1.9
42.3
4190
78
1400
AMA 450L6L
33
990
96.2
96.6
0.87
0.86
161
5.1
44
13502
0.7
2.0
46.8
4430
78
1600
AMA 500L6L
34
991
96.3
96.7
0.88
0.87
181
5.3
47
15418
0.8
2.0
65.5
5210
79
1800
AMA 500L6L
35
991
96.4
96.8
0.89
0.88
203
5.3
51
17344
0.8
2.0
72.8
5500
79
2000
AMA 500L6L
473
991
96.5
96.9
0.89
0.88
224
5.3
53
19272
0.8
2.0
80.1
5800
79
2250
AMA 500L6L
474
991
96.6
97.0
0.89
0.89
251
5.4
59
21678
0.8
2.0
87.4
6090
79
750 r/min = 8 poles
6000 V 50 Hz
315
AMA 400L8L
36
739
94.0
94.5
0.84
0.81
39
4.6
14
4070
0.8
1.8
17.6
2690
75
355
AMA 400L8L
37
739
94.0
94.5
0.84
0.81
43
4.6
16
4586
0.8
1.8
19.0
2790
75
400
AMA 400L8L
38
739
94.5
94.9
0.84
0.81
49
4.7
17
5166
0.8
1.8
20.4
2880
75
450
AMA 400L8L
39
739
94.5
95.0
0.84
0.82
54
4.6
19
5815
0.8
1.8
21.8
2980
75
500
AMA 400L8L
40
739
94.6
95.1
0.84
0.82
60
4.6
21
6461
0.8
1.8
23.3
3070
75
560
AMA 400L8L
41
739
94.8
95.2
0.84
0.81
68
4.7
24
7234
0.9
1.8
24.7
3160
75
630
AMA 450L8L
42
742
95.3
95.7
0.83
0.80
76
5.2
29
8109
0.8
2.1
38.0
3670
76
710
AMA 450L8L
43
742
95.4
95.8
0.83
0.80
86
5.3
33
9138
0.8
2.1
40.7
3800
76
800
AMA 450L8L
44
741
95.5
96.0
0.86
0.84
94
4.7
29
10311
0.7
1.8
46.1
4030
76
900
AMA 450L8L
45
741
95.7
96.1
0.86
0.84
105
4.8
32
11598
0.7
1.8
51.5
4270
76
1000
AMA 500L8L
46
739
95.5
96.1
0.87
0.86
116
4.5
32
12914
0.7
1.8
66.7
4870
77
1120
AMA 500L8L
47
739
95.6
96.2
0.87
0.86
129
4.5
33
14464
0.7
1.8
75.5
5170
77
1250
AMA 500L8L
48
741
95.9
96.4
0.87
0.86
144
4.7
38
16101
0.7
1.8
85.0
5440
77
1400
AMA 500L8L
49
742
96.2
96.5
0.87
0.85
161
5.2
48
18011
0.8
2.0
93.9
5750
77
1600
AMA 500L8L
475
742
96.2
96.6
0.87
0.86
184
5.0
51
20596
0.7
1.9
102.8
6040
77
Data presented in rating lists are typical values.
Guaranteed values on request. All engineered motors
are optimized for the specified application. Accurate
motor data will be given on request at quotation phase.
Legally binding performance and specification data is